Sel 735 Manual «EASY »»

| Parameter | Default | Typical Change | |-----------|---------|----------------| | PT ratio | 1:1 | 4160:120 | | CT ratio | 1:1 | 200:5 | | Demand interval | 15 min | 15 or 30 min | | Sag threshold | 90% of nominal | 90% | | Swell threshold | 110% | 110% | | THD alarm level | 5% | 8% per IEEE 519 |

: Provides comprehensive details on operation, including 4-quadrant metering and time-of-use reporting. sel 735 manual

If your meter firmware is R100-V2 , you need the manual revision that matches firmware version R200 or lower. | Parameter | Default | Typical Change |

"If you lose network access, use the rear RS-232 port to reset Ethernet settings via the IP command." Manufactured by Schweitzer Engineering Laboratories (SEL)

The SEL 735 is a highly advanced and versatile relay device designed for use in power systems. Manufactured by Schweitzer Engineering Laboratories (SEL), this device is widely used in the utility and industrial power markets for applications such as line protection, transformer protection, and bus protection. The SEL 735 manual is a detailed guide that provides users with a comprehensive understanding of the device's features, installation, operation, and maintenance.